КПСЭ нг(А)-FRFH 2×1.0mm² shielded Fire Alarm Cable
КПСЭ нг(А)-FRFH 2×1.0mm² shielded Fire Alarm Cable
КПСЭ нг(А)-FRFH 2×1.0mm² shielded
Fire Alarm Cable
|
|
|
Cable construction :
|
Conductor:
|
Bare copper class 12×1.13mm
|
|
|
Insulation:
|
Type: Silicone Dia.over Dielectric: 0.094''''nom.(2.4mm)
|
|
|
Insulation Color:
|
Blu/Brn
|
Separator :
|
PET Foil
|
Drain Wire:
|
0.4 mm Solid tinned copper
|
Shield:
|
Aluminum PET (100% Coverage 20% overlapping)
|
Jacket:
|
FRFH-LSOH
|
Dia.over Jacket: 0.248''''(6.3mm)
|
Print Legend:
|
HELLOSIGNAL NO.7110564 КПСЭ нг(А)-FRFH 2×1.0mm² shielded Cable MMDDYYYY
|
|
Electrical Properties :
|
Minimum Bend Radius
|
8×Diameter
|
Min.DC resistance
|
18.8 ohm/KM
|
Min.Insulation resistance
|
100 MΩ/km
|
Installation Temperature
|
-10℃~+50℃
|
Test voltage (rms value)
|
1000V
|
Max. Operating Voltage
|
300 V
|
|
Test Standards
|
√180 minutes under fire of 750 degrees without short-circuit.
|
√Fire hazard class of the cable on the classification of ГОСТ Р 31565-2012 - P1.1.2.2.2.
|
√Cable flame retardant while installing in category A (ГОСТ Р IEC 60332-3-22-2005).
|
√Indicator toxicity of the combustion products of polymeric material of the cable - not less than 41g / m.
|
√Smoke generation during combustion and smoldering cable does not reduce the light transmittance of more than 50% (GOST R IEC 61034-2-2005).
|
√The cable is designed for fixed installation for voltage to 300 V AC to 10 kHz or 420 VDC.
|
|
|